Prepared For:
Sample Customer
Property Address:
1234 Main St
Somewhere, IL
![]() |
| Date: 10/12/2005 | Time: 5:28 AM | Report ID: 101205 |
| Property: 1234 Main St Somewhere, IL |
Customer: Sample Customer |
Real Estate Professional: Sample Realtor |
Comment Key or Definitions
The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property.
Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing for normal wear and tear.
Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting.
Not Present (NP) = This item, component or unit is not in this home or building.
Repair or Replace (RR) = The item, component or unit is not functioning as intended or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.
| Style of Home: Ranch |
Age Of Home: Over 40 Years |
Home Faces: East |
| Client Is
Present: Yes |
Radon Test: No |
Water Test: No |
| Weather: Light Rain |
Temperature: Below 60 |
Rain in last 3
days: Yes |
| ROOF COVERING: ARCHITECTURAL |
VIEWED ROOF COVERING
FROM: GROUND WALKED ROOF |
SKY LIGHT (S): VENTILATING MOTORIZED |
| CHIMNEY (exterior): BRICK METAL FLUE PIPE |
| IN | NI | NP | RR | ||
| 1.0 | ROOF COVERINGS | X | |||
| 1.1 | FLASHINGS | X | |||
| 1.2 | SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONS | X | X | ||
| 1.3 | ROOFING DRAINAGE SYSTEMS | X | X | ||
| IN | NI | NP | RR | ||
![]() 1.3 Picture 1 |
![]() 1.3 Picture 2 |
![]() 1.3 Picture 3 |
![]() 1.3 Picture 4 |
| SIDING MATERIAL: WOOD BRICK VENEER |
| IN | NI | NP | RR | ||
| 2.0 | WALL CLADDING FLASHING AND TRIM | X | X | ||
| 2.1 | DOORS (Exterior) | X | |||
| 2.2 | WINDOWS | X | |||
| 2.3 | DECKS, BALCONIES, STOOPS, STEPS, AREAWAYS, PORCHES AND APPLICABLE RAILINGS | X | |||
| 2.4 | VEGETATION, GRADING, DRAINAGE, DRIVEWAYS, PATIOS, WALKWAYS AND RETAINING WALLS (With respect to their effect on the condition of the building) | X | X | ||
| 2.5 | EAVES, SOFFITS AND FASCIAS | X | |||
| IN | NI | NP | RR | ||
![]() 2.0 Picture 1 |
![]() 2.0 Picture 2 |
![]() 2.4 Picture 1 |
![]() 2.4 Picture 2 |
![]() 2.4 Picture 3 |
| ATTIC INSULATION: BLOWN BATT |
VENTILATION: PASSIVE |
| IN | NI | NP | RR | ||
| 3.0 | INSULATION AND VAPOR RETARDERS (in unfinished spaces) | X | X | ||
| 3.1 | VENTILATION OF ATTIC AND FOUNDATION AREAS | X | |||
| 3.2 | VENTING SYSTEMS (Kitchens, baths and laundry) | X | X | ||
| 3.3 | VENTILATION FANS AND THERMOSTATIC CONTROLS (ATTIC) | X | |||
| IN | NI | NP | RR | ||
![]() 3.0 Picture 1 |
![]() 3.0 Picture 2 |
![]() 3.2 Picture 1 |
![]() 3.2 Picture 2 |
| CEILING MATERIALS: SHEETROCK |
WALL MATERIAL: SHEETROCK |
| IN | NI | NP | RR | ||
| 4.0 | CEILINGS | X | |||
| 4.1 | WALLS | X | |||
| 4.2 | FLOORS | X | |||
| 4.3 | STEPS, STAIRWAYS, BALCONIES AND RAILINGS | X | |||
| 4.4 | COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS | X | |||
| 4.5 | DOORS (REPRESENTATIVE NUMBER) | X | |||
| 4.6 | WINDOWS (REPRESENTATIVE NUMBER) | X | X | ||
| IN | NI | NP | RR | ||
![]() 4.6 Picture 1 |
| FOUNDATION: POURED CONCRETE |
WALL STRUCTURE: 2 X 4 WOOD |
ROOF-TYPE: HIP |
| METHOD USED TO OBSERVE
ATTIC: WALKED |
ATTIC INFO: PULL DOWN STAIRS |
| IN | NI | NP | RR | ||
| 5.0 | FOUNDATIONS (Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components.) | X | |||
| 5.1 | WALLS (Structural) | X | X | ||
| 5.2 | COLUMNS OR PIERS | X | |||
| 5.3 | FLOORS (Structural) | X | |||
| 5.4 | CEILINGS (structural) | X | |||
| 5.5 | ROOF STRUCTURE AND ATTIC | X | |||
| IN | NI | NP | RR | ||
![]() 5.1 Picture 1 |
![]() 5.1 Picture 2 |
| WATER SOURCE: PUBLIC |
PLUMBING SUPPLY: COPPER GALVANIZED |
WATER HEATER POWER
SOURCE: GAS (QUICK RECOVERY) |
| MANUFACTURER: A.O. SMITH |
| IN | NI | NP | RR | ||
| 6.0 | INTERIOR DRAIN, WASTE AND VENT SYSTEMS | X | X | ||
| 6.1 | INTERIOR WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES | X | X | ||
| 6.2 | HOT WATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND VENTS | X | X | ||
| 6.3 | MAIN WATER SHUT-OFF DEVICE (Describe location) | X | |||
| 6.4 | FUEL STORAGE AND DISTRIBUTION SYSTEMS (Interior fuel storage, piping, venting, supports, leaks) | X | |||
| IN | NI | NP | RR | ||
![]() 6.0 Picture 1 |
![]() 6.1 Picture 1 |
![]() 6.1 Picture 2 |
![]() 6.1 Picture 3 |
![]() 6.2 Picture 1 |
| ELECTRICAL SERVICE
CONDUCTORS: BELOW GROUND |
PANEL CAPACITY: 200 AMP |
PANEL TYPE: CIRCUIT BREAKERS |
| BRANCH WIRE 15 and 20
AMP: COPPER |
| IN | NI | NP | RR | ||
| 7.0 | SERVICE ENTRANCE CONDUCTORS | X | |||
| 7.1 | SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION PANELS | X | |||
| 7.2 | BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR AMPERAGE AND VOLTAGE | X | |||
| 7.3 | CONNECTED DEVICES AND FIXTURES (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls) | X | X | ||
| 7.4 | POLARITY AND GROUNDING OF RECEPTACLES WITHIN 6 FEET OF INTERIOR PLUMBING FIXTURES, AND ALL RECEPTACLES IN GARAGE, CARPORT, EXTERIOR WALLS OF INSPECTED STRUCTURE | X | X | ||
| 7.5 | OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTERS) | X | |||
| 7.6 | LOCATION OF MAIN AND DISTRIBUTION PANELS | X | |||
| 7.7 | SMOKE DETECTORS | X | |||
| IN | NI | NP | RR | ||
![]() 7.3 Picture 1 |
![]() 7.3 Picture 2 |
![]() 7.3 Picture 3 |
![]() 7.4 Picture 1 |
| HEAT TYPE: FORCED AIR |
ENERGY SOURCE: GAS |
NUMBER OF HEAT SYSTEMS (excluding
wood): ONE |
| TYPES OF FIREPLACES: SOLID FUEL VENTED GAS LOGS |
OPERABLE FIREPLACES: THREE |
NUMBER OF WOODSTOVES: NONE |
| IN | NI | NP | RR | ||
| 8.0 | HEATING EQUIPMENT | X | |||
| 8.1 | NORMAL OPERATING CONTROLS | X | |||
| 8.2 | CHIMNEYS, FLUES AND VENTS | X | |||
| 8.3 | SOLID FUEL HEATING DEVICES | X | |||
| 8.4 | HEAT DISTRIBUTION SYSTEMS (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units and convectors) | X | |||
| 8.5 | GAS/LP FIRELOGS AND FIREPLACES | X | X | ||
| 8.6 | PRESENCE OF INSTALLED HEAT SOURCE IN EACH ROOM | X | |||
| IN | NI | NP | RR | ||
| COOLING EQUIPMENT ENERGY
SOURCE: ELECTRICITY |
NUMBER OF A/C UNITS: ONE |
| IN | NI | NP | RR | ||
| 9.0 | COOLING AND AIR HANDLER EQUIPMENT | X | |||
| 9.1 | NORMAL OPERATING CONTROLS | X | |||
| 9.2 | DISTRIBUTION SYSTEMS (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units and convectors) | X | |||
| 9.3 | PRESENCE OF INSTALLED COOLING SOURCE IN EACH ROOM | X | |||
| IN | NI | NP | RR | ||
| IN | NI | NP | RR | ||
| 10.0 | DISHWASHER | X | |||
| 10.1 | RANGES/OVENS/COOKTOPS | X | |||
| 10.2 | RANGE HOOD | X | |||
| 10.3 | TRASH COMPACTOR | X | |||
| 10.4 | FOOD WASTE DISPOSER | X | |||
| 10.5 | MICROWAVE COOKING EQUIPMENT | X | |||
| IN | NI | NP | RR | ||
![]() Accurate Home Inspections NW Corp 2303 Magnolia St. | |
|
Customer | |
|
Home | |
| 1.2 | SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONS | |||||
| Inspected, Repair or Replace | ||||||
|
Lead boot on west roof does not cover plumbing
vent pipe. Exposed kitchen ceiling is present. Recommend repair by a
qualified licenced roofer.
| ||||||
|
Recommend installing elbow to keep water and
debris from entering.
| ||||||
| 1.3 | ROOFING DRAINAGE SYSTEMS | |||||
| Inspected, Repair or Replace | ||||||
|
Several miters at gutters leak, recommend
downspouts drain six feet away from house.
| ||||||
| 2.0 | WALL CLADDING FLASHING AND TRIM | ||||
| Inspected, Repair or Replace | |||||
|
Siding at west and northwest is damaged, this
is for your information.
| |||||
| 2.4 | VEGETATION, GRADING, DRAINAGE, DRIVEWAYS, PATIOS, WALKWAYS AND RETAINING WALLS (With respect to their effect on the condition of the building) | ||||
| Inspected, Repair or Replace | |||||
|
Tree limbs over hanging house may damage roof,
recommend trimming.
| |||||
| 3.0 | INSULATION AND VAPOR RETARDERS (in unfinished spaces) | |||
| Inspected, Repair or Replace | ||||
|
Insulation missing above kitchen and north of
kitchen.
| ||||
| 3.2 | VENTING SYSTEMS (Kitchens, baths and laundry) | |||
| Inspected, Repair or Replace | ||||
|
Recommend bath exost vents through the roof,
not in the attic.
| ||||
| 4.6 | WINDOWS (REPRESENTATIVE NUMBER) | ||
| Inspected, Repair or Replace | |||
|
Auto shut-off does not work on master hall
skylight.
| |||
| 5.1 | WALLS (Structural) | |||
| Inspected, Repair or Replace | ||||
|
North addition is separated from main house,
may want to seek opinion of a qualified structural engineer.
| ||||
| 6.0 | INTERIOR DRAIN, WASTE AND VENT SYSTEMS | ||
| Inspected, Repair or Replace | |||
|
Plumbing vent at back door appears to be
clogged with debris, recommend inspection by a qualified licenced
plumber.
| |||
| 6.1 | INTERIOR WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES | ||
| Inspected, Repair or Replace | |||
|
Lav drain in master bath did not close all the
way at time of inspection.
| |||
|
Damaged hose at bathtub at master bath.
| |||
|
Unfinished supply in basement shower.
| |||
| 6.2 | HOT WATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND VENTS | ||
| Inspected, Repair or Replace | |||
|
Living room chimney damper appears to be
in disrepair, I did not attempt to operate for fear of injury.
| |||
| 7.3 | CONNECTED DEVICES AND FIXTURES (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls) | ||||
| Inspected, Repair or Replace | |||||
|
Hall light dims sometimes when kitchen lights
are turned on, open ground at living room next to piano, hot/neutral
reversed in east BR, west wall, recommend inspection and repair by a
qualified electrician.
| |||||
| 7.4 | POLARITY AND GROUNDING OF RECEPTACLES WITHIN 6 FEET OF INTERIOR PLUMBING FIXTURES, AND ALL RECEPTACLES IN GARAGE, CARPORT, EXTERIOR WALLS OF INSPECTED STRUCTURE | ||||
| Inspected, Repair or Replace | |||||
|
Recommend GFCI within 6' of plumbing
fixture.
| |||||
| 7.7 | SMOKE DETECTORS | ||||
| Repair or Replace | |||||
|
Recommend all new smoke detectors before
moving into home. | |||||
| 8.5 | GAS/LP FIRELOGS AND FIREPLACES | |
| Inspected, Repair or Replace | ||
|
Gas fireplace in south addition did not work
at time of inspection, gas heater in garage did not work at time of
inspection. | ||
| 9.0 | COOLING AND AIR HANDLER EQUIPMENT | |
| Not Inspected | ||
|
A/C was not tested for proper operation due to
the outside air temperature is 65 degrees or less. We did not inspect this
unit (S). | ||
Prepared Using HomeGauge http://www.homegauge.com/ SHGI (c)
2000-2004 : Licensed To Accurate Home Inspections NW Corp
1.2 Picture 1
1.2 Picture 2
1.2 Picture 3
Recommend installing elbow to keep water and debris from entering.
1.2 Picture 4
1.2 Picture 5